Plan Review Notes For Permit 00111365 |
Permit Number |
00111365 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************DENIED******************* | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62-89, DEFINE SPACES CLEARLY AS | | TO USE, (BEAUTY SALONS REQUIRE MORE O/A | | THAN SOME OTHER OCCUPANCIES.) | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | COMPLIANCE W/ 1997 SMC 501.2 | | 3. NOTE TABLE 1205 1997 SMC REQUIRES ALL | | CHILLED WATER PIPE IN COPPER TO BE | | BRAZED, NOT SOLDERED. | | 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | REQUIRED FOR ALL UNITS SERVING AREAS W/ | | COMBINED AIR TOTALING 2000 CFM OR MORE | | OR UNITS W/ LESS THAN 2000 CFM BUT SERV- | | ING AREAS USED FOR EGRESS. |
|