Plan Review Notes For Permit 00111365 |
Permit Number |
00111365 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ******************* UNSAT ************* | | | | 1)NOTE: PLEASE PROVIDE CLARIFICATION | | FOR BUS AMPS SHOWN AS ???FOR "GCH" | | | | 2)NOTE: PLEASE SEE COLOR CODING OF LOCAL | | AMNEDMENTS OF 277/480 ART215 | | | | 3)NOTE: PLEASE SEE 450-13B AND SUBMIT | | CLARIFICATION ON TRANSFORMER INSTALL- | | ATION. NOT ALLOWED ABOVE CEILING OVER | | 50KVA. | | | | 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS | | LOADS ARE TO BE FIGURED AT 125% LIGHTING | | AND LARGEST MOTOR. 215-2 | | | | 5)NOTE: PLEASE NOTE THAT NO BRANCH | | CIRCUIT CONDUCTOR SIZES ARE SHOWN ON | | PANEL SCHEDULES? PLEASE ADJUST. | | | | 6)NOTE:PLEASE SEE RISER DIAGRAM NO COND- | | -UCTOR SIZES AND CONDUIT SIZES FROM | | PANEL"GCH" TO TRANSFORMER AND TO "GCL" | | PLEASE SHOW. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 |
|