2001-01-08 00:00:00******************* UNSAT *************
  
 1)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR BUS AMPS SHOWN AS ???FOR "GCH"
  
 2)NOTE: PLEASE SEE COLOR CODING OF LOCAL
 AMNEDMENTS OF 277/480 ART215
  
 3)NOTE: PLEASE SEE 450-13B AND SUBMIT
 CLARIFICATION ON TRANSFORMER INSTALL-
 ATION. NOT ALLOWED ABOVE CEILING OVER
 50KVA.
  
 4)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE FIGURED AT 125% LIGHTING
 AND LARGEST MOTOR. 215-2
  
 5)NOTE: PLEASE NOTE THAT NO BRANCH
 CIRCUIT CONDUCTOR SIZES ARE SHOWN ON
 PANEL SCHEDULES? PLEASE ADJUST.
  
 6)NOTE:PLEASE SEE RISER DIAGRAM NO COND-
 -UCTOR SIZES AND CONDUIT SIZES FROM
 PANEL"GCH" TO TRANSFORMER AND TO "GCL"
 PLEASE SHOW.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW