Plan Review Notes For Permit 00111239 |
Permit Number |
00111239 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED; | | | | 1.MENS ROOM MUST HAVE A URINAL. SPC | | TABLE 407 NOTE # 3 | | | | 2.CALCULATE USABLE SQUIRE FOOTAGE PER | | 407.1.3 TO FIND REQUIRED BATHROOM | | FACILITYS IN TABLE 407 | | | | 3.HANDICAP BATHROOMS MUST MEET REQUIRE- | | MENTS OF THE 97 FACBC CODE FOR | | REMODELING. | | | | 4.SHOW RESTAURANT EQUIPMENT SCHEDULE | | AND LOCATION OF EQUIPMENT.INDIRECT | | DRAINAGES TO DRAIN INTO FLOOR SINKS. | | | | 5.SHOW SANITARY RISER FOR KITCHEN | | EQUIPMENT. | | | | 6.GREASE TRAP REQUIREMENTS BY UTILITYS | | RODNEY COMPO ORD. #2938-96. | | | | 7.SHOW H2O RISER DIAGRAM. | | | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|