2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: SMOKE DETECTORS ARE REQ`D INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS PER
 NFPA-72 2-2.1.1.1
  
 2)NOTE: PLEASE SEE THE AIC RATING FOR
 BRKRS AT PANEL WERE SUBMITTED. THIS IS
 CORRECT AND NEEDED BUT NO AIC RATING FOR
 MAIN WAS SHOWN. PLEASE DO SO. PER 110-9
  
 3)NOTE: PLEASE CLARIFY ANY OF THE GFI
 CIRCUITS SHOWN ON PANEL SCHEDULEFOR
 BATH(S). PER 210-11-C-3
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESITONS
 PLEASE CALL.
  