2001-01-09 00:00:00 | ***************** UNSAT *************** | | | | 1)NOTE:PLEASE SHOW ALL MEANS OF EGRESS | | LIGHTING REQ`D PER 210-70 OF THE NEC. | | | | 2)NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GF/GFI | | PROCTECTED PER 210-8-A-6. | | | | 3)NOTE: PLEASE SEE MISSING OUTLETS PER | | 210-52. 2`,6`,12` RULE. | | | | PLEASE REVISE AND SUBMIT THE ABOVE INFOR | | MATION FOR REVIEW BEFORE FINAL ELECTRICA | | L INSPECTION IS CALLED IN. IF THERE ARE | | ANY QUESTIONS PLEASE CALL. | | | | DEWEY PLAMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|