2001-02-23 00:00:00*******************DENIED***************
  
 PROVIDE CALCULATIONS FOR VENTILATION IN
 MECHANICAL ROOM AS PER 1997 SMC 1105.7.1
  
 PROVIDE DETAIL FOR RELIEF VENT PIPING
 AND TERMINATION AS PER 1997 SMC 1105.9.
 ALSO INDICATE REFRIGERANT LEAK
 DETECTOR WITH HORN/STROBE OUTSIDE
 ENTRANCE TO MECHANICAL ROOM AS WELL AS
 IN MECHANICAL ROOM AS REQUIRED PER 97
 SMC 1105.3.
  
 INDICATE LOCATION OF BREATHING
 APPARATUS 97 SCM 1105.8.
  
 SHOW WHERE MAKE-UP AIR IS FOR THE
 EXISTING AHU THAT SUPPLIES A CORE AREA.