Plan Review Notes For Permit 00110939 |
Permit Number |
00110939 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-02-23 00:00:00 | *******************DENIED*************** | | | | PROVIDE CALCULATIONS FOR VENTILATION IN | | MECHANICAL ROOM AS PER 1997 SMC 1105.7.1 | | | | PROVIDE DETAIL FOR RELIEF VENT PIPING | | AND TERMINATION AS PER 1997 SMC 1105.9. | | ALSO INDICATE REFRIGERANT LEAK | | DETECTOR WITH HORN/STROBE OUTSIDE | | ENTRANCE TO MECHANICAL ROOM AS WELL AS | | IN MECHANICAL ROOM AS REQUIRED PER 97 | | SMC 1105.3. | | | | INDICATE LOCATION OF BREATHING | | APPARATUS 97 SCM 1105.8. | | | | SHOW WHERE MAKE-UP AIR IS FOR THE | | EXISTING AHU THAT SUPPLIES A CORE AREA. |
|