2001-01-08 00:00:00DENIED
  
 1)BUILDING OFFICIAL WILL NOT ACCEPT ROOM
 LABELED DEN/STUDY AS SHOWN WITHOUT
 EXTERIOR EMERGENCY ESCAPE AND RESCUE
 OPENING AS REQUIRED BY 97 SBC 1005.4.
  
 2)PROVIDE INSTALLATION SCHEDULE FOR
 STORM PANELS.
  
 3)SUBMIT 2 REVISED COPIES OF KEY PLAN
 FOR THIS UNIT. THE KEY PLAN SUBMITTED
 SHOWS WINDOWS IN THE 2 HOUR WALL AND
 DOES NOT MATCH THE FOOTPRINT OF THE
 BUILDING.
  
 4)PROVIDE PRODUCT APPROVALS FOR WINDOW
 MULLIONS.