Plan Review Notes
Plan Review Notes For Permit 00110764
Permit Number 00110764
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY OF W.P.B. BUILDING
 DEPT. BEFORE A PERMIT CAN BE ISSUED.
  
 2)UNLABELED ROOM ADJACENT TO LIVING ROOM
 MUST COMPLY WITH SECTION 1203 OF THE
 1997 STANDARD BUILDING CODE FOR LIGHT
 AND VETILATION.
 SECTION 1203.1.5 ALLOWS WINDOWS TO BE
 OMITTED IN HABITABLE ROOMS IF ADEQUATE
 ADEQUATE LIGHT AND VENTILATION ARE
 PROVIDED THROUGH OTHER SOURCES APPROVED
 BY THE BUILDING OFFICIAL.
 PLEASE PROVIDE SPECIFIC DETAILS AS TO
 WHICH METHODS WILL BE USED TO MEET THESE
 REQUIREMENTS.
  
 3)THE UNLABELED ROOM MUST HAVE AT LEAST
 ONE EXTERIOR EMERGENCY ESCAPE AND RESCUE
 OPENING,IF IT IS USED AS A SLEEPING ROOM
 PER 1005.4.1 OF 97 SBC (SEE EXCEPTIONS).
 ALTHOUGH THERE IS NO CLOSET IN THIS ROOM
 IT COULD BE USED AS A BEDROOM. BEDROOM
 #2 SHOWN ON THE PLANS ALSO HAS NO CLOSET
  
 4)PROVIDE INSTALLATION SCHEDULE FOR
 STORM PANELS.
  
 5)THE KEY PLAN PROVIDED DOES NOT COMPLY
 WITH THE ARCHITECTURAL DRAWINGS. PLEASE
 SUBMIT (2) COPIES OF REVISED KEY PLAN.
  
 6)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR THE
 FOLLOWING ITEMS:
 -SLIDING GLASS DOORS
 -MULLIONS
  
 7)PROVIDE PRODUCT APPROVALS FOR ROOF
 COVERING UNDER SEPARATE PERMIT.