2002-01-22 00:00:00*************** UNSAT ******************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 2) PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 FRONT MISSING
  
 3) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 SHOWN ON ONE PANEL, BUT NOT THE OTHER?
  
 5)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52 H
  
 6)NOTE: PLEASE NOTE CLEARENCE FOR AHU
 DISC, FIRST FLOOR 110-26. ORIG PLANS
 SHOW DISC IN UNIT?
  
 7)NOTE: PLEASE NOTE MISSING FOOTER STEEL
 PER 250-50 AND ON ORIG PLANS?
  
 8)NOTE: PLEASE NOTE PANELS ARE SHOWN
 AT 150A AND PANEL SCHEDULES ARE SHOWN AT
 300AMPS??
  
 9)NOTE: PLEASE NOTE POOL HEATER SHOWN ON
 PANEL SCHEDULES BUT NOT, IN LOAD CALCS??
  
 10)NOTE: PLEASE NNOTE TWO 3000W WATER
 HEATERS SHOWN ON SCHEDULES, BUT ONLY
 ONE 4500W ON LOAD CALCS???
  
 11)NOTE: PLEASE NOTE, PLANS ARE STILL
 SHOWING EXISTING HOUSE GL? PLEASE NOTE
 THIS IS NOT REALLY EXSITING SINCE THE
 ENTIRE STRUCTURE IS RE-DONE?
 PLEASE CLARIFY PLANS SHOW NEW FRONT
 HOUSE SERVICE? AND WHAT ABOUT SERIVCE TO
 ANY OTHER HOUSE? IS THERE ARE "BACK"
 HOUSE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372