Plan Review Notes
Plan Review Notes For Permit 00110723
Permit Number 00110723
Review Stop R
Sequence Number 3
Notes
Date Text
2001-07-17 00:00:001-FRENCH DOORS PRODUCT APPROVAL THAT WAS
 SUBMITTED IS GOOD ONLY FOR DOUBLE
 DOORS AS SHOWN ON APPROVED DRAWINGS.
 -NEED TO PROVIDE PRODUCT APPROVAL FOR
 FRENCH DOORS WITH SIDELITES SINGLE
 ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS
 2-PROVIDE PRODUCT APPROVAL FOR:
 -FIXED WINDOWS.
 -ROUND WINDOWS.
 -EXTERIOR SWING SINGLE DOORS.
 -ENTRY DOOR WITH SIDELITES AND TRANSOM
 ABOVE AS SHOWN ON ARCHITECT'S PLANS.
 3-TRUSS DRAWINGS:
 A)TRUSS ENGINEER TO PROVIDE ALL HIS INFO
 ON TRUSS LAYOUT AS REQUIRED BY CHAPTER
 471 OF FLORIDA STATUTES.
 B)TRUSS ENGINEER TO HAVE ORIGINAL
 SIGNATURE ON ALL ENGINEERED TRUSSES AS
 REQUIRED BY CHAPTER 471 FL. STATUTES.
 C)TRUSS ENGINEER TO UPDATE ALL GENERAL
 TRUSS DETAILS. USE ASCE 7-95 (NOT 93)
 FOR 145MPH.
 ALSO, PROVIDE ORIGINAL SIGNATURE AND
 DATE OF SEALING THE DRAWING. CH. 471.
 D)ENGINEERED TRUSSES TO BE REVISED USING
 ASCE 7-95 FOR 145MPH (NOT 140MPH).
 E)TRUSS LAYOUT AND ARCHITECT'S ROOF
 FRAMING PLAN ARE DIFFERENT. ROOF TRUSS
 LAYOUT CALLS FOR A 4" COL. TO SUPPORT
 TRUSS MG16. REVISE PLANS SHOWING THE
 RIGHT COLUMN SIZE AND CONNECTIONS AT
 SECOND FLOOR AND ROOF AREA.
 -ALSO, PROVIDE COLUMN DETAIL SHOWING
 SUPPORT OF TRUSS FG-7 AND FG-9.
 F)CONNECTOR SPECIFIED FOR TRUSS HG-13
 DOESN'T RESIST THE LOADS CALCULATED ON
 THE ENGINEERED TRUSSES. REVISE AS
 REQUIRED.