Date |
Text |
2001-07-17 00:00:00 | 1-FRENCH DOORS PRODUCT APPROVAL THAT WAS |
| SUBMITTED IS GOOD ONLY FOR DOUBLE |
| DOORS AS SHOWN ON APPROVED DRAWINGS. |
| -NEED TO PROVIDE PRODUCT APPROVAL FOR |
| FRENCH DOORS WITH SIDELITES SINGLE |
| ASSEMBLY AS SHOWN ON ARCHITECT'S PLANS |
| 2-PROVIDE PRODUCT APPROVAL FOR: |
| -FIXED WINDOWS. |
| -ROUND WINDOWS. |
| -EXTERIOR SWING SINGLE DOORS. |
| -ENTRY DOOR WITH SIDELITES AND TRANSOM |
| ABOVE AS SHOWN ON ARCHITECT'S PLANS. |
| 3-TRUSS DRAWINGS: |
| A)TRUSS ENGINEER TO PROVIDE ALL HIS INFO |
| ON TRUSS LAYOUT AS REQUIRED BY CHAPTER |
| 471 OF FLORIDA STATUTES. |
| B)TRUSS ENGINEER TO HAVE ORIGINAL |
| SIGNATURE ON ALL ENGINEERED TRUSSES AS |
| REQUIRED BY CHAPTER 471 FL. STATUTES. |
| C)TRUSS ENGINEER TO UPDATE ALL GENERAL |
| TRUSS DETAILS. USE ASCE 7-95 (NOT 93) |
| FOR 145MPH. |
| ALSO, PROVIDE ORIGINAL SIGNATURE AND |
| DATE OF SEALING THE DRAWING. CH. 471. |
| D)ENGINEERED TRUSSES TO BE REVISED USING |
| ASCE 7-95 FOR 145MPH (NOT 140MPH). |
| E)TRUSS LAYOUT AND ARCHITECT'S ROOF |
| FRAMING PLAN ARE DIFFERENT. ROOF TRUSS |
| LAYOUT CALLS FOR A 4" COL. TO SUPPORT |
| TRUSS MG16. REVISE PLANS SHOWING THE |
| RIGHT COLUMN SIZE AND CONNECTIONS AT |
| SECOND FLOOR AND ROOF AREA. |
| -ALSO, PROVIDE COLUMN DETAIL SHOWING |
| SUPPORT OF TRUSS FG-7 AND FG-9. |
| F)CONNECTOR SPECIFIED FOR TRUSS HG-13 |
| DOESN'T RESIST THE LOADS CALCULATED ON |
| THE ENGINEERED TRUSSES. REVISE AS |
| REQUIRED. |