Plan Review Notes
Plan Review Notes For Permit 00110723
Permit Number 00110723
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-25 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. NOTE #2 PANEL SCHEDULE USED TO
 SHOW 300A MAINS AND WAS ASKED TO
 CORRELATE WITH PANELS SHOWN ON RISER
 DIAGRAM. NOW PANELS DON'T SHOWN ANY
 MAIN BRKR RATING.
  
 2)NOTE: PLEASE SEE NOTE 3 FROM FIRST
 REVIEW. PLANS SAY TO SEE ATTACHED
 LETTER FROM FPL.NO LETTER FOUND, BUT
 A LETTER FROM FPL ONLYS TELLS ME THE
 AVAILABLE FAULT CURRENT RATING AT
 TRANSFORMER. PLANS NEED TO INDICATE THE
 RATING OF EQUIPMENT BEING INSTALLED.
 THIS IS REQ`D TO BE ON PLANS. PER 110-9
 AND 215-5.
  
 3)NOTE: PLEASE VERIFY WATER HEATER
 WATTAGES. 2400W IS NOT A TYPICAL SIZE?
 JUST NOTE.
  
  
 4)NOTE: NOT NOTED ON FIRST REVIEW, GROUN
 DING ELECTRODE CONDUCTOR TO BE SHOWN TO
 BUILDING STEEL ALSO PER 250-50.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
  
 REVIEW. PLEASE, IF THERE ARE ANY QUESTIO
 NS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372