2001-01-25 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | REVIEW. NOTE #2 PANEL SCHEDULE USED TO | | SHOW 300A MAINS AND WAS ASKED TO | | CORRELATE WITH PANELS SHOWN ON RISER | | DIAGRAM. NOW PANELS DON'T SHOWN ANY | | MAIN BRKR RATING. | | | | 2)NOTE: PLEASE SEE NOTE 3 FROM FIRST | | REVIEW. PLANS SAY TO SEE ATTACHED | | LETTER FROM FPL.NO LETTER FOUND, BUT | | A LETTER FROM FPL ONLYS TELLS ME THE | | AVAILABLE FAULT CURRENT RATING AT | | TRANSFORMER. PLANS NEED TO INDICATE THE | | RATING OF EQUIPMENT BEING INSTALLED. | | THIS IS REQ`D TO BE ON PLANS. PER 110-9 | | AND 215-5. | | | | 3)NOTE: PLEASE VERIFY WATER HEATER | | WATTAGES. 2400W IS NOT A TYPICAL SIZE? | | JUST NOTE. | | | | | | 4)NOTE: NOT NOTED ON FIRST REVIEW, GROUN | | DING ELECTRODE CONDUCTOR TO BE SHOWN TO | | BUILDING STEEL ALSO PER 250-50. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | | REVIEW. PLEASE, IF THERE ARE ANY QUESTIO | | NS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|