2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES ON ME-1. THE
 TOP OF THE NOTES SAY ALL NOTES BELOW
 PERTAIN TO THIS PLAN. PLEASE SEE NOTES,,
 CASH REGISTER? FUSED MAIN DISCONNECTS??
 PLEASE CLARIFY.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULES AND
 RISER,,, RISER SHOWS 150A MAINS AND
 PANEL SCH SHOWS 300A MAINS??? PLEASE
 CORRELATE.
  
 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL MAINS AND BREAKERS. ALL MAINS/PANELS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT PER 110-9
  
 4)NOTE: PLEASE SEE LOAD CALCULATIONS,,,
 WHIRLPOOL IN MB SHOWN?? PLEASE SEE
 PANEL SCHED.?? AND PLAN DOES NOT SHOW
 IN MASTER BATH.
  
 5)NOTE: PLEASE SEE LOAD CALCS. WATER
 HEATER SHOWN AT 4500W`S. THIS ALSO DOES-
 -NOT CORRELATE WITH PANEL SCHEDULES.
 PANELS SHOW MORE THAN ONE WATER HEATER??
 ALSO THE LOAD FOR WATER HEATERS FOR BOTH
 NEED TO CORRELATE W/ LOAD CALCS.
  
 6)NOTE: POOL HEATER SHOWN ON PANEL SCHED
 -ULE BUT NOT SHOWN ON LOAD CALCS. ?????
 PLEASE DO SO.
  
 7)NOTE: PLEASE CLARIFY THE MAIN?METER
 COMBO. ALSO PLEASE SHOW ALL EQUIPMENT
 AND SHOW LOCATIONS OF ALL EQUIPMENT ON
 PLANS/PANELS/METER ETC.
  
 THE FOLLOWING IS FOR E-1.0
  
 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP-
 -ING ROOMS AND ON EACH LEVEL OF DWELLING
 PER NFPA-72 2-2.1.1.1 PLEASE SHOW ALL
 REQ`D.
  
 2)NOTE: PLEASE SEE MISSING GFI OUTLETS
 PER 210-52E FRONT AND REAR OF DWELLING.
  
 3)NOTE: PLEASE SEE MISSING OUTLETS FOR
 HALLWAY(S) PER 210-52H
  
 4)NOTE: PLEASE SEE MISSING OUTLETS SPAC-
 -ING PER 210-52
  
 5)NOTE: PLEASE SEE LOCATIONS SHOWN FOR
 DISCONNECTS THROUGHOUT HOUSE. MUST MEET
 110-26 FOR CLEARENCE REQ`MENTS.
  
 6)NOTE: PLEASE SEE MISSING OUTLETS PER
 MECH CODE FOR CONDENSING UNITS. WP GFI`S
 309-1.
  
 THE FOLLOWING IS FOR SECOND FLOOR E-2.0
  
 MOST OF THE SAME NOTES FROM FIRST FLOOR
 FOR SD`S, OUTLET SPACING AND DISCONNECT
 CLEARENCE.
  
  
 PLEASE SHOW AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  