2001-01-08 00:00:00 | *************** UNSAT ***************** |
| |
| 1)NOTE: PLEASE SEE NOTES ON ME-1. THE |
| TOP OF THE NOTES SAY ALL NOTES BELOW |
| PERTAIN TO THIS PLAN. PLEASE SEE NOTES,, |
| CASH REGISTER? FUSED MAIN DISCONNECTS?? |
| PLEASE CLARIFY. |
| |
| 2)NOTE: PLEASE SEE PANEL SCHEDULES AND |
| RISER,,, RISER SHOWS 150A MAINS AND |
| PANEL SCH SHOWS 300A MAINS??? PLEASE |
| CORRELATE. |
| |
| 3)NOTE: PLEASE PROVIDE AIC RATINGS FOR |
| ALL MAINS AND BREAKERS. ALL MAINS/PANELS |
| MUST BE RATED FOR THE AVAILABLE FAULT |
| CURRENT PER 110-9 |
| |
| 4)NOTE: PLEASE SEE LOAD CALCULATIONS,,, |
| WHIRLPOOL IN MB SHOWN?? PLEASE SEE |
| PANEL SCHED.?? AND PLAN DOES NOT SHOW |
| IN MASTER BATH. |
| |
| 5)NOTE: PLEASE SEE LOAD CALCS. WATER |
| HEATER SHOWN AT 4500W`S. THIS ALSO DOES- |
| -NOT CORRELATE WITH PANEL SCHEDULES. |
| PANELS SHOW MORE THAN ONE WATER HEATER?? |
| ALSO THE LOAD FOR WATER HEATERS FOR BOTH |
| NEED TO CORRELATE W/ LOAD CALCS. |
| |
| 6)NOTE: POOL HEATER SHOWN ON PANEL SCHED |
| -ULE BUT NOT SHOWN ON LOAD CALCS. ????? |
| PLEASE DO SO. |
| |
| 7)NOTE: PLEASE CLARIFY THE MAIN?METER |
| COMBO. ALSO PLEASE SHOW ALL EQUIPMENT |
| AND SHOW LOCATIONS OF ALL EQUIPMENT ON |
| PLANS/PANELS/METER ETC. |
| |
| THE FOLLOWING IS FOR E-1.0 |
| |
| 1)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| ARE REQ`D INSIDE AND OUTSIDE ALL SLEEP- |
| -ING ROOMS AND ON EACH LEVEL OF DWELLING |
| PER NFPA-72 2-2.1.1.1 PLEASE SHOW ALL |
| REQ`D. |
| |
| 2)NOTE: PLEASE SEE MISSING GFI OUTLETS |
| PER 210-52E FRONT AND REAR OF DWELLING. |
| |
| 3)NOTE: PLEASE SEE MISSING OUTLETS FOR |
| HALLWAY(S) PER 210-52H |
| |
| 4)NOTE: PLEASE SEE MISSING OUTLETS SPAC- |
| -ING PER 210-52 |
| |
| 5)NOTE: PLEASE SEE LOCATIONS SHOWN FOR |
| DISCONNECTS THROUGHOUT HOUSE. MUST MEET |
| 110-26 FOR CLEARENCE REQ`MENTS. |
| |
| 6)NOTE: PLEASE SEE MISSING OUTLETS PER |
| MECH CODE FOR CONDENSING UNITS. WP GFI`S |
| 309-1. |
| |
| THE FOLLOWING IS FOR SECOND FLOOR E-2.0 |
| |
| MOST OF THE SAME NOTES FROM FIRST FLOOR |
| FOR SD`S, OUTLET SPACING AND DISCONNECT |
| CLEARENCE. |
| |
| |
| PLEASE SHOW AND SUBMIT ALL THE ABOVE |
| INFORMATION FOR REVIEW. IF THERE ARE ANY |
| QUESTIONS PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |
| 561-659-8096 EXT 8372 |