Plan Review Notes For Permit 00110340 |
Permit Number |
00110340 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PROVISO: | | 1.ALL THREE AHU'S REQUIRE FAN SHUT DOWN | | BY DUCT SMOKE DETECTOR W/ NOTIFICATION | | BY BLDG FIRE ALARM SYSTEM. | | 2.NO COMBUSTIBLES IN R/A PLENUM AREA | | ABOVE CEILING |
|