Plan Review Notes
Plan Review Notes For Permit 00110340
Permit Number 00110340
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1.ALL THREE AHU'S REQUIRE FAN SHUT DOWN
 BY DUCT SMOKE DETECTOR W/ NOTIFICATION
 BY BLDG FIRE ALARM SYSTEM.
 2.NO COMBUSTIBLES IN R/A PLENUM AREA
 ABOVE CEILING