2001-01-08 00:00:00ON DECEMBER 11, 2000, WRITER ALONG WITH
 PLUMBING PLAN REVIEWER JOHN LEECH
 EXAMINED THE INFORMATION FOR PERMIT
 00110332. SEVERAL CONCERNS WERE RAISED
 BY JOHN LEECH AND THIS WRITER. ON SAME
 DATE, WRITER CONTACTED MARK KAPLAN OF
 BRADLEY HEATING AND A/C, INC.
 ACCORDING TO MR. KAPLAN THE PROPANE
 TANKS ARE APPROXIMATELY 25 FEET FROM
 OTHER BUILDINGS. THIS INFORMATION IS
 NOT SHOWN ON THE DRAWINGS. HE ALSO
 ADVISED THAT THE PROPANE TANKS ARE
 APPROXIMATELY 25 FEET FROM PROPERTY
 LINES. HE FURTHER ADVISED THAT GAS
 PIPING WILL BE DONE BY OTHERS. HE
 ALSO ADVISED THAT HE BELIEVES THAT
 THIS PIPING WILL BE 1/2 INCH GALVANIZED
 OR BLACK AND WOULD PROBABLY BE CLAMPED
 OR UNISTRUTED TO THE BUILDING.HE ALSO
 STATED THAT NO DOORS ARE PRESENT ALONG
 THE SIDE OF THE BUILDING NEAR THE
 PROPANE STORAGE.
 1) NO SMOKING SIGNS ARE TO BE PROVIDED.
 2) COMPLIANCE WITH NFPA 704 IS
 REQUIRED.
 3) COMPLIANCE WITH NFPA 58 IS REQUIRED.