2001-01-08 00:00:00 | ON DECEMBER 11, 2000, WRITER ALONG WITH | | PLUMBING PLAN REVIEWER JOHN LEECH | | EXAMINED THE INFORMATION FOR PERMIT | | 00110332. SEVERAL CONCERNS WERE RAISED | | BY JOHN LEECH AND THIS WRITER. ON SAME | | DATE, WRITER CONTACTED MARK KAPLAN OF | | BRADLEY HEATING AND A/C, INC. | | ACCORDING TO MR. KAPLAN THE PROPANE | | TANKS ARE APPROXIMATELY 25 FEET FROM | | OTHER BUILDINGS. THIS INFORMATION IS | | NOT SHOWN ON THE DRAWINGS. HE ALSO | | ADVISED THAT THE PROPANE TANKS ARE | | APPROXIMATELY 25 FEET FROM PROPERTY | | LINES. HE FURTHER ADVISED THAT GAS | | PIPING WILL BE DONE BY OTHERS. HE | | ALSO ADVISED THAT HE BELIEVES THAT | | THIS PIPING WILL BE 1/2 INCH GALVANIZED | | OR BLACK AND WOULD PROBABLY BE CLAMPED | | OR UNISTRUTED TO THE BUILDING.HE ALSO | | STATED THAT NO DOORS ARE PRESENT ALONG | | THE SIDE OF THE BUILDING NEAR THE | | PROPANE STORAGE. | | 1) NO SMOKING SIGNS ARE TO BE PROVIDED. | | 2) COMPLIANCE WITH NFPA 704 IS | | REQUIRED. | | 3) COMPLIANCE WITH NFPA 58 IS REQUIRED. |
|