2001-01-08 00:00:00 | 1) BOLLARDS ARE REQUIRED TO PROTECT TANK | | FROM MECHANICAL DAMAGE. | | 2) STORAGE TANK TO BE LABELED IN | | ACCORDANCE WITH NFPA 704. ALSO NO | | SMOKING LABELS AND PRODUCT NAME TO BE | | PLACED ON TANK. | | 3) PLEASE PROVIDE CUT SHEETS ON STORAGE | | TANK. | | 4) VENT PIPE TO BE AT LEAST 1 1/4 AND | | AT LEAST 12 FEET FROM THE GROUND. | | 5) TANK AND ASSOCIATED PIPING TO COMPLY | | WITH CITY CODE REQUIREMENTS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|