Plan Review Notes
Plan Review Notes For Permit 00110196
Permit Number 00110196
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) BOLLARDS ARE REQUIRED TO PROTECT TANK
 FROM MECHANICAL DAMAGE.
 2) STORAGE TANK TO BE LABELED IN
 ACCORDANCE WITH NFPA 704. ALSO NO
 SMOKING LABELS AND PRODUCT NAME TO BE
 PLACED ON TANK.
 3) PLEASE PROVIDE CUT SHEETS ON STORAGE
 TANK.
 4) VENT PIPE TO BE AT LEAST 1 1/4 AND
 AT LEAST 12 FEET FROM THE GROUND.
 5) TANK AND ASSOCIATED PIPING TO COMPLY
 WITH CITY CODE REQUIREMENTS.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910