Plan Review Notes
Plan Review Notes For Permit 00110185
Permit Number 00110185
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOW THE PLANS
 ARE SHOWING A METER/MAIN COMBO, BUT NOT
 SHOWING AIC RATING FOR THIS. PLEASE
 SUBMIT PER 110-9 AND 215-5.
  
 2)NOTE: PLEASE SEE PLANS, THE MAIN IS
 NOT SHOWN WITH METER. PLEASE DO SO.
  
 3)NOTE: ALSO PLEASE VERIFY PANEL "A"
 YOU SHOW ON RISER AS PANEL W/ MCB.
 YOU HAVE MAIN ALREADY. PLEASE CHECK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372