Notes |
Date |
Text |
2001-01-10 00:00:00 | 1) PLEASE CLEARLY INDICATE THE OCCUPANCY | | TYPES FOR THE TWO BAYS. | | 2) EXITING NOT PERMITTED THROUGH STORAGE | | ROOM. | | 3) ELECTRICAL PLANS DO NOT DISPLAY | | EXISTING EMERGENCY LIGHTS OR ILLUMINATED | | EXIT SIGNS WITHIN THE TWO BAYS. | | 4) ANY OPENING PROTECTIVE DEVICE PLANNED | | FOR THE TWO HOUR WALL. | | 5) EXITING IS NOT VERY CLEAR TO WRITER | | ON THE DEAD-END STREET SIDE. | | 6) CLEARLY INDICATE THE TWO MEANS OF | | EGRESS FROM THE BAY LOCATED ADJACENT TO | | THE PARKING LOT. | | 7) PLANS DO NOT INDICATE TYPE X FIRE | | RATED DRYWALL. PLEASE PROVIDE WALL | | DETAIL AND APPLICABLE UL NUMBER. | | 8) NO INTERIOR FINISH INFORMATION | | LOCATED ON PLANS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|