2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: AIC RATINGS ARE SUBMITTED FOR
 PANELS BUT NOT FOR MAIN. PLEASE SUBMIT
 AIC RATING FOR MAIN ALSO. NOTE; MAINS
 MUST BE RATED FOR THE AVAIABLE FAULT
 CURRENT PER 110-9 AND SHOW PER 215-5.
  
 2)NOTE:PLEASE SHOW DETAIL FOR GROUND
 ATTACHMENT AT 16KVA UPS. PLEASE CLARIFY
 NOTE NEXT TO UPS AS (LCOCATION) 1ST FL.?
  
  
 3)NOTE: PLEASE SHOW LOCATION OF NEW 400A
 DISC AND EXISTING SERVICE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  