Plan Review Notes For Permit 00110160 |
Permit Number |
00110160 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: AIC RATINGS ARE SUBMITTED FOR | | PANELS BUT NOT FOR MAIN. PLEASE SUBMIT | | AIC RATING FOR MAIN ALSO. NOTE; MAINS | | MUST BE RATED FOR THE AVAIABLE FAULT | | CURRENT PER 110-9 AND SHOW PER 215-5. | | | | 2)NOTE:PLEASE SHOW DETAIL FOR GROUND | | ATTACHMENT AT 16KVA UPS. PLEASE CLARIFY | | NOTE NEXT TO UPS AS (LCOCATION) 1ST FL.? | | | | | | 3)NOTE: PLEASE SHOW LOCATION OF NEW 400A | | DISC AND EXISTING SERVICE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|