Plan Review Notes
Plan Review Notes For Permit 00110155
Permit Number 00110155
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS,,, BOTH GAS AND
 ELEC HEAT PUMP IS NOT SHOWN ON WIRING
 DIAGRAM?? PLEASE DO SO.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTION
 FOR ALL NEW LOADS BEING INTRODUCED ON
 EXISTING ELECTRICAL SERVICE.PLEASE SHOW
 EXISTING SERVICE SIZE.
  
 PLEASE SUBMIR THE ABOVE INFORMATON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372