2001-02-16 00:00:00***************DENIED*******************
  
 DRAWING M-1 INDICATES RECONFIGURATION
 OF DROPS IN KITCHEN AREA AND ADDITIONAL
 DROPS.THIS BRINGS THE TOTAL CFM'S FOR
 THIS AHU UP TO 1160, 2 TON UNIT IS ON
 AIR HANDLER SCHEDULE (DWG MP-1).
  
 CALLED AND SPOKE WITH ALLEN, MADE HIM
 AWARE OF THE PROBLEM.HE INDICATED THE
 UNIT SHOULD BE A 4 TON UNIT.WILL
 CORRECT THE PROBLEM.
  
 PHK 2/16/01