Plan Review Notes
Plan Review Notes For Permit 00101480
Permit Number 00101480
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) PLEASE CLARIFY BATTERY ROOM. WHAT
 TYPE OF BATTERIES, HOW MANY, WHAT ARE
 THEY USED FOR, AND WHAT IF ANY DANGER
 DO THEY POSE.
 2) PLEASE PROVIDE COMPLETE FIRE ALARM
 SYSTEM SHOP DRAWINGS FOR THE FIRE ALARM
 EQUIPMENT SHOWN ON THE PLANS. CUT SHEETS
 WIRING DIAGRAM, AND FLOOR PLAN ARE
 NEEDED WHEN SUBMITTED UNDER SEPARATE
 PERMIT.
 3) PLEASE SUBMIT COMPLETE FIRE SPRINKLER
 DRAWINGS FOR THE PRE-ACTION FIRE
 SPRINKLER SYSTEM SHOWN ON THE DRAWINGS.
 A SEPARATE PLAN AND PERMIT REQUIRED.
  
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910