Plan Review Notes
Plan Review Notes For Permit 00101480
Permit Number 00101480
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE:PLEASE NOTE THAT A DISCONNECT IS
 REQ`D INLINE FROM GENERATOR TO ATS. PER
 230-70/225-31 AND GROUPING OF DISCONNECT
 PER 230-72 AND 225-34 AND LOCATION PER
 225-32.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION
 FOR GFI PROTECTION OF SERVICE PER 230-95
  
  
 3)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 NOT SUBMITTED FOR NEW PANELS SHOWN ON
 6TH FLOOR.
  
 PLEASE CLARIFY FIRE PUMP(S) AND IF
 EXISTING AND WHERE THEY ARE CONNECTED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
  
 561-659-8096 EXT 8372
  
  
 4)NOTE: PLEASE NOTE THAT ALL OUTLET
 SPACING IS TO MEET LOCAL CODE ART:210-50
 OFFICES= EVERY 12` AND STORAGE AREAS
 EVERY 20` OF UNENCUMBERED WALL SPACE.