Plan Review Notes For Permit 00101480 |
Permit Number |
00101480 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE:PLEASE NOTE THAT A DISCONNECT IS | | REQ`D INLINE FROM GENERATOR TO ATS. PER | | 230-70/225-31 AND GROUPING OF DISCONNECT | | PER 230-72 AND 225-34 AND LOCATION PER | | 225-32. | | | | 2)NOTE: PLEASE PROVIDE CLARIFICATION | | FOR GFI PROTECTION OF SERVICE PER 230-95 | | | | | | 3)NOTE: PLEASE SUBMIT PANEL SCHEDULES | | NOT SUBMITTED FOR NEW PANELS SHOWN ON | | 6TH FLOOR. | | | | PLEASE CLARIFY FIRE PUMP(S) AND IF | | EXISTING AND WHERE THEY ARE CONNECTED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | | | 561-659-8096 EXT 8372 | | | | | | 4)NOTE: PLEASE NOTE THAT ALL OUTLET | | SPACING IS TO MEET LOCAL CODE ART:210-50 | | OFFICES= EVERY 12` AND STORAGE AREAS | | EVERY 20` OF UNENCUMBERED WALL SPACE. |
|