Plan Review Notes
Plan Review Notes For Permit 00101378
Permit Number 00101378
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 BOTH RTU'S WILL NEED FAN SHUT DOWN BY
 DUCT SMOKE DETECTOR AS THE AIR IS INTER-
 MIXED IN COMMON SPACE.