Plan Review Notes
Plan Review Notes For Permit 00101312
Permit Number 00101312
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT RISER DIAGRAM SHOWING PIPE SIZES,
 SLOPE OF PIPE,SQUARE FOOTAGE DRAINED BY
 EACH DRAIN.COMPLY W/SPC TABLES 1108.1,
 1108.2.,1107.3.
  
 2)STORMWATER DISCHARGE SHALL NOT BE TO
 AN AREA THAT WILL CREATE A NUISANCE.
 CLEARLY SHOW TERMINATION POINT OF DRAINS
 SPC 301.4.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.