2001-01-08 00:00:00 | ************** UNSAT ****************** |
| |
| 1)NOTE: AS ASKED FOR AND REQ`D FROM |
| FIRST REVIEW. PLEASE SUBMIT AIC RATING |
| FOR MAIN AND PANELS. PER 110-9/215-5 |
| |
| 2)NOTE: PLEASE NOTE ALL OUTLETS SERVING |
| KITCHEN COUNTERSPACE ARE TO BE GFI/GFI |
| PROTECTED PER 210-8-A-6 PLEASE SHOW |
| |
| 3)NOTE: PLEASE SEE MISSING SD LOWER |
| LEVEL. |
| |
| 4)NOTE: PLEASE NOTE THAT THE PLANS ARE |
| NOW SHOWING COMPLETE REWIRE? IF CATV |
| AND TELEPHONES ARE GOING TO BE INSTALLED |
| THEN THEY MUST BE ON PLAN??? |
| |
| 5)NOTE: PLEASE NOTE THAT NO PANEL SCHED- |
| -ULE WAS SUBMITTED AND MISSING BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. AS ASKED FOR |
| ON PREVIOUS REVIEW. |
| |
| 6)NOTE: PLEASE SEE LOAD CALCULATIONS? |
| YOU SHOW TWO SEPARATE A/C UNITS? PLEASE |
| SHOW THESE ON PLANS AND SHOW DISCONNECTS |
| PER 440-11 AND GFI PER MECH CODE 309.1 |
| PLEASE SHOW IN HOUSE AHU`S. |
| AS ON PREVIOUS NOTE IF THERE ARE EXIST- |
| -ING ELECTRICAL CONDITIONS?? PLEASE SHOW |
| AND PROVIDE CLARIFICATION. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 659-8096 EXT 8372 |