Plan Review Notes
Plan Review Notes For Permit 00101227
Permit Number 00101227
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: AS ASKED FOR AND REQ`D FROM
 FIRST REVIEW. PLEASE SUBMIT AIC RATING
 FOR MAIN AND PANELS. PER 110-9/215-5
  
 2)NOTE: PLEASE NOTE ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE ARE TO BE GFI/GFI
 PROTECTED PER 210-8-A-6 PLEASE SHOW
  
 3)NOTE: PLEASE SEE MISSING SD LOWER
 LEVEL.
  
 4)NOTE: PLEASE NOTE THAT THE PLANS ARE
 NOW SHOWING COMPLETE REWIRE? IF CATV
 AND TELEPHONES ARE GOING TO BE INSTALLED
 THEN THEY MUST BE ON PLAN???
  
 5)NOTE: PLEASE NOTE THAT NO PANEL SCHED-
 -ULE WAS SUBMITTED AND MISSING BATH(S)
 CIRCUIT(S) PER 210-11-C-3. AS ASKED FOR
 ON PREVIOUS REVIEW.
  
 6)NOTE: PLEASE SEE LOAD CALCULATIONS?
 YOU SHOW TWO SEPARATE A/C UNITS? PLEASE
 SHOW THESE ON PLANS AND SHOW DISCONNECTS
 PER 440-11 AND GFI PER MECH CODE 309.1
 PLEASE SHOW IN HOUSE AHU`S.
 AS ON PREVIOUS NOTE IF THERE ARE EXIST-
 -ING ELECTRICAL CONDITIONS?? PLEASE SHOW
 AND PROVIDE CLARIFICATION.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372