Plan Review Notes For Permit 00101227 |
Permit Number |
00101227 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE: NO ELECTRICAL WAS SUBMITTED FOR | | NEW ADDITION AREA. PLEASE SUBMIT. | | | | 2)NOTE: THE ELECTRICAL THAT WAS SUBMIT- | | -TED FOR SECOND FLOOR IS FOR WHAT? IS | | THIS AREA BEING REWIRED? IF SO PLEASE | | MAKE NOTE ON PLANS FOR CLARIFICATION. | | | | 3)NOTE: ALSO PLEASE NOTE THAT A SD WILL | | BE REQ`D ON THE FIRST LEVEL AT THE BOT- | | -TOMOF THE STAIRS,,, NFPA-72 | | | | 4)NOTE: PLEASE SUBMIT AIC RATING FOR | | ALL EQUIPMENT BEING INSTALLED. PER 110-9 | | AND 215-5 | | | | 5)NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) ON PANEL SCHEDULE PER 210-52D | | AND 210-11-C-3 | | | | 6)NOTE: PLEASE NOTE THAT IF THERE IS | | GOING TO BE ANY CATV OR TELEPHONES | | UPSTAIRS THEN PLEASE DRAW ON PLAN. IF | | THEY ARE EXISTING THEN DISREGUARD. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|