Plan Review Notes
Plan Review Notes For Permit 00101227
Permit Number 00101227
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: NO ELECTRICAL WAS SUBMITTED FOR
 NEW ADDITION AREA. PLEASE SUBMIT.
  
 2)NOTE: THE ELECTRICAL THAT WAS SUBMIT-
 -TED FOR SECOND FLOOR IS FOR WHAT? IS
 THIS AREA BEING REWIRED? IF SO PLEASE
 MAKE NOTE ON PLANS FOR CLARIFICATION.
  
 3)NOTE: ALSO PLEASE NOTE THAT A SD WILL
 BE REQ`D ON THE FIRST LEVEL AT THE BOT-
 -TOMOF THE STAIRS,,, NFPA-72
  
 4)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL EQUIPMENT BEING INSTALLED. PER 110-9
 AND 215-5
  
 5)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) ON PANEL SCHEDULE PER 210-52D
 AND 210-11-C-3
  
 6)NOTE: PLEASE NOTE THAT IF THERE IS
 GOING TO BE ANY CATV OR TELEPHONES
 UPSTAIRS THEN PLEASE DRAW ON PLAN. IF
 THEY ARE EXISTING THEN DISREGUARD.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372