Plan Review Notes For Permit 00100919 |
Permit Number |
00100919 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-04-05 00:00:00 | **************** UNSAT***************** | | | | 1)NOTE: PLEASE PROVIDE BRANCH CIRCUIT | | #`S ON PLANS THAT CORRELATE WITH PANEL | | SCHEDULES. | | | | 2)NOTE:PLEASE REMOVE HALL SWITCHING,AS | | HALL/STAIRWAY IS NOW ON SEPARATE PLANS. | | | | 3)NOTE: PLEASE NOTE THAT LOADS SHOWN FOR | | TWO PANELS EXCEED OVERCURRENT PROTECTION | | OF DISCONNECT. | | | | 4)NOTE: PLEASE NOTE THAT MEANS OF EGRESS | | LIGHTING COMING INTO TENANT#2 IS SHOWN G | | OING TO CEILING J-BOX. PLEASE NOTE THAT | | SOME SORT OF MIN LIGHTING FIXTURES ARE | | REQ`D. 210-70 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. PLEASE GET WITH ON ANY QUESTIONS | | OR CLARIFICATION THAT IS NEEDED. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|