Plan Review Notes
Plan Review Notes For Permit 00100823
Permit Number 00100823
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN DISCONNECT.
 ALSO PLEASE SHOW METER MAIN ON PLAN ON
 OUTSIDE OF HOUSE.
 MAIN MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT PER 110-9.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372