2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN DISCONNECT. AIC RATING IS SHOWN FOR
 PANEL"A" BUT AIC RATINGS ARE TO SUBMITT-
 -ED FOR ALL SERVICE EQUIPMENT BEING
 INSTALLED. PER 110-9 AND 215-5.
  
 2)NOTE: PLEASE DRAW IN DISCONNECT/METER
 ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCIAL PLAN REVIEW
 659-8096 EXT 8372