Plan Review Notes For Permit 00100763 |
Permit Number |
00100763 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) PLANS DO NOT INDICATE LOCATIONS OF | | REQUIRED EMERGENCY LIGHTS OR ILLUMINATED | | EXIT SIGNS. | | 2) DOOR 4 DOES NOT PROVIDE PROPER EXIT | | WIDTH TO EXIT DOOR. | | 3) NO INTERIOR FINISH INFORMATION NOTED | | ON PLANS. | | 4) SEATING DIAGRAM NOT PROVIDED WITH | | PLANS TO DETERMINE OCCUPANT LOAD OR | | EXIT CAPACITIES. | | 5) A SINGLE STEP TO COUNTER BAR AREA IS | | NOT PERMITTED. CHANGES IN ELEVATION | | LESS THAN 21 INCHES SHALL BE BY RAMPS. | | STEPS WHEN USED ARE TO TOTAL THREE AT | | 7 INCHES EACH. | | 6) PROVISIONS ARE TO BE MADE FOR AT | | TWO HANDICAPPED PERSONS. | | 7) IF OCCUPANT LOAD IS TO BE DETERMINED | | AT 100 OR MORE PERSONS, PANIC HARDWARE | | IS REQUIRED ON ALL EXIT DOORS. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|