2001-01-08 00:00:001) PLAN REVIEW COMMENTS INDICATE THAT
 NO FIRE SPRINKLERS ARE PRESENT. SINCE
 THERE ARE NO FIRE SPRINKLERS, DEAD-END
 CORRIDORS CANNOT EXCEED 20 FEET. HALL
 # 3 EXCEEDS DEAD-END CORRIDOR ALLOWANCE
 FOR BUSINESS OCCUPANCIES WITHOUT
 FIRE SPRINKLERS.
  