Plan Review Notes For Permit 00100505
Permit Number 00100505
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
 SUBMIT UL ASSEMBLY NUMBER AND DETAIL FOR
 FIRESAFING OF METALLIC AND NON- METALLIC
 PIPE PENETRATIONS.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.4.
  
 2)SHT.A115-DELETE REFERENCE TO SO.FLA.
 BLDG.CODE.THE CODES IN EFFECT IN THE
 CITY OF WPB ARE THEW STANDARD CODES.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.
  
 3)FLUSH CONTROLS ON WATER CLOSETS IN
 HANDICAP TOILET ROOMS SHALL BE LOCATED
 ON THE WIDE SIDE PER FACBC SEC.4.16.5.
  
 4)SUBMIT ISOMETRIC FOR THE REVISED STORM
 WATER DRAINAGE SYSTEM.SHOW SQ.FOOT AREA
 DRAINED BY EACH ROOF DRAIN.COMPLY W/SPC
 SEC.1108.1,1108.2.
  
 5)PROVIDE INFORMATION ON SECONDARY
 DRAINAGE.COMPLY W/SPC SEC.1109.
  
 CALL IF YOU HAVE QUESTIONS
 561-659-8096,EXT.8377.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.