Plan Review Notes For Permit 00100505 |
Permit Number |
00100505 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | | | SUBMIT UL ASSEMBLY NUMBER AND DETAIL FOR | | FIRESAFING OF METALLIC AND NON- METALLIC | | PIPE PENETRATIONS.COUNTYWIDE AMENDMENTS | | TO SPC SEC.104.2.4. | | | | 2)SHT.A115-DELETE REFERENCE TO SO.FLA. | | BLDG.CODE.THE CODES IN EFFECT IN THE | | CITY OF WPB ARE THEW STANDARD CODES. | | COUNTYWIDE AMENDMENTS TO SPC SEC.101. | | | | 3)FLUSH CONTROLS ON WATER CLOSETS IN | | HANDICAP TOILET ROOMS SHALL BE LOCATED | | ON THE WIDE SIDE PER FACBC SEC.4.16.5. | | | | 4)SUBMIT ISOMETRIC FOR THE REVISED STORM | | WATER DRAINAGE SYSTEM.SHOW SQ.FOOT AREA | | DRAINED BY EACH ROOF DRAIN.COMPLY W/SPC | | SEC.1108.1,1108.2. | | | | 5)PROVIDE INFORMATION ON SECONDARY | | DRAINAGE.COMPLY W/SPC SEC.1109. | | | | CALL IF YOU HAVE QUESTIONS | | 561-659-8096,EXT.8377. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|