Plan Review Notes For Permit 00100505 |
Permit Number |
00100505 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | COMPLY WITH CITY CODE REQUIREMENTS. | | 2) PLEASE EXPLAIN EXITING. IT APPEARS | | THAT ALL DESIGNATED EXITS ARE ON ONE | | SIDE OF THE BUILDING. WHEN EXITS ARE | | REQUIRED THEY ARE TO BE SEPARATED FROM | | ONE ANOTHER SO A SINGLE FIRE CANNOT | | BLOCK BOTH EXITS. | | 3) PLEASE SHOW FIRE HYDRANT LOCATIONS. | | 4) PLEASE INDICATE HOW VEHICLES WILL | | BE DISPLAYED WITHIN BUILDING. | | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|