Plan Review Notes For Permit 00100406 |
Permit Number |
00100406 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-09 00:00:00 | ****************DENIED****************** | | 1. RISER DIAGRAM SHOWS FIRE DAMPERS AT | | EACH FLOOR FOR THE EXHAUST DUCT. 1997 | | SMC610.4 REQUIRES THAT IN ALL BUILDINGS | | MORE THAN ONE FLOOR IN HEIGHT, DUCTS | | EXTENDING THROUGH MORE THAN ONE FLOOR | | TO BE PROTECTED BY A SHAFT ENCLOSURE | | HAVING A FIRE RESISTANCE RATING OF NOT | | LESS THAN 2 HOURS IN BUILDINGS FOUR | | FLOORS OR MORE IN HEIGHT. PROVIDE SHAFT | | DETAIL AND FIRE DAMPER LOCATION FOR | | DUCTS LEAVING SHAFT AS REQUIRED BY | | 610.1.2 |
|