2001-01-09 00:00:00****************DENIED******************
 1. RISER DIAGRAM SHOWS FIRE DAMPERS AT
 EACH FLOOR FOR THE EXHAUST DUCT. 1997
 SMC610.4 REQUIRES THAT IN ALL BUILDINGS
 MORE THAN ONE FLOOR IN HEIGHT, DUCTS
 EXTENDING THROUGH MORE THAN ONE FLOOR
 TO BE PROTECTED BY A SHAFT ENCLOSURE
 HAVING A FIRE RESISTANCE RATING OF NOT
 LESS THAN 2 HOURS IN BUILDINGS FOUR
 FLOORS OR MORE IN HEIGHT. PROVIDE SHAFT
 DETAIL AND FIRE DAMPER LOCATION FOR
 DUCTS LEAVING SHAFT AS REQUIRED BY
 610.1.2