Plan Review Notes For Permit 00100247 |
Permit Number |
00100247 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-02-28 00:00:00 | ************* UNSAT ************ | | | | 1)NOTE: PLEASE SEE SHEET 2 OF 4 THIS IS | | SHOWING A NEW ELECTRICAL SERVICE AND | | 3 OF 4 SAYS EXISTING? | | | | 2)NOTE: PLEASE NOTE LOAD CALCULATIONS | | FOR MAIN SERVICE WAS NOT SUBMITTED SHOW- | | ING ALL CONTINUOUS LOADS AT 125%. | | | | 3)NOTE: PLEASE SEE 3 OF 4 "PLAN NOTES" | | #3 SHOWS 4-1/0`S AND #6G. THIS IS SHOWN | | AS A 1PHASE SERVICE. PLEASE CLARIFY. | | | | 4)NOTE:PLEASE NOTE THAT ALL ELECTRICAL | | POWER FEEDING PAVILLIONS REQ MEANS OF | | DISCONNECT PER 225-31. | | | | PLEASE SUBMIT THE ABOVE CLARIFICATION | | AND INFORMATION FOR REVIEW. IF THERE ARE | | ANY QUESTIONS OR IF CORRECTIONS CAN BE | | TAKEN CARE OF IN PERSON, PLEASE CALL | | TO SSET UP A TIME FOR A MEETING. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|