Plan Review Notes
Plan Review Notes For Permit 00100247
Permit Number 00100247
Review Stop E
Sequence Number 2
Notes
Date Text
2001-02-28 00:00:00************* UNSAT ************
  
 1)NOTE: PLEASE SEE SHEET 2 OF 4 THIS IS
 SHOWING A NEW ELECTRICAL SERVICE AND
 3 OF 4 SAYS EXISTING?
  
 2)NOTE: PLEASE NOTE LOAD CALCULATIONS
 FOR MAIN SERVICE WAS NOT SUBMITTED SHOW-
 ING ALL CONTINUOUS LOADS AT 125%.
  
 3)NOTE: PLEASE SEE 3 OF 4 "PLAN NOTES"
 #3 SHOWS 4-1/0`S AND #6G. THIS IS SHOWN
 AS A 1PHASE SERVICE. PLEASE CLARIFY.
  
 4)NOTE:PLEASE NOTE THAT ALL ELECTRICAL
 POWER FEEDING PAVILLIONS REQ MEANS OF
 DISCONNECT PER 225-31.
  
 PLEASE SUBMIT THE ABOVE CLARIFICATION
 AND INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS OR IF CORRECTIONS CAN BE
 TAKEN CARE OF IN PERSON, PLEASE CALL
 TO SSET UP A TIME FOR A MEETING.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372