Plan Review Notes
Plan Review Notes For Permit 00100247
Permit Number 00100247
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)A WATER USE PERMIT IS REQD.FROM SO.FLA
 WATER MNGMT.DIV.FOR THE IRRIGATION
 SYSTEM PER F.S.373.219.SUBMIT COPY OF
 PERMIT.
  
 2)A WELL DRILLING PERMIT WILL ALSO BE
 REQD.FROM SFWMD AND P.B.COUNTY HEALTH
 DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 3)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 4)DOOR SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQD.FOR THE DRINKING
 FOUNTAINS.(A MIN.30"X48"CLEAR SPACE IS
 REQD.FACBC SEC.4.15.5.
  
 5)SHT.P-1-NOTE #5-CALCULATED AIR CHAMBER
 SHALL COMPLY W/STANDARD PDI-WH201.SPC
 SEC.607.8.2.
  
 6)SHOW SINK AND DRINKING FOUNTAIN ON
 WATER RISER ON SHT.P-1.COUNTYWIDE AMEND-
 MENT TO SPC SEC.104.2.1.
  
 CALL IF YOU HAVE QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.