Notes |
Date |
Text |
2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | SHOWING ALL CONTINUOUS LOADS AT 125% | | LIGHTING ETC.SHEET E-3 OF 4 SHOWS CON- | | -CESSION PANEL AS BEING BY OTHERS?? | | PLEASE SUBMIT CLARIFICATION? | | PANEL FOR CONCESSION BLDG IS ON 4 OF 4? | | CONTINUOUS LOADS FOR PANEL "L" ALSO. | | | | 2)NOTE: PLEASE SEE NOTE #3 NOTE DESCRIBE | | -S 4-1/0`S FOR FEED TO PANEL"L". SHOWS | | MAIN BREAKER AT 60AMPS. PLEASE CALRIFY | | 1/0 WIRE SIZE INTO 60A BRKR. | | | | 3)NOTE: PLEASE SEE 110-26 AND 384-7 FOR | | PANEL REQ`MENTS IN A "STORAGE ROOM". | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 |
|