Notes
Date Text
2001-01-08 00:00:00***************PROVISO******************
  
 1)ARCHITECT TO PROVIDE REVISED SHEET A-5
 ROOF FRAMING PLAN WITH INDENTIFYING TAG
 MARKS WHICH CORRESPOND WITH TRUSS ANCHOR
 SCHEDULE ON SHEET A-4. CLEARLY SPECIFY
 THE CONNECTORS THAT ARE TO BE USED ON
 EACH SPECIFIC TRUSS OR GROUPS OF TRUSSES
 DRAWINGS MUST BE SUBMITTED AND APPROVED
 PRIOR TO POURING OF TIE BEAM.
  
 2)PROVIDE ENGINEERED UPLIFT CALCULATIONS
 OR SPECIFY PRODUCT CODE AND MANUFACTURER
 FOR CONNECTORS DETAILED ON SHEET A-6 #S
 12,13,14 & 15 PRIOR TO TIE BEAM POUR.
  
 3)PROVIDE PRODUCT APPROVALS, KEY PLAN &
 INSTALLATION SCHEDULE FOR STORM PANELS
 UNDER A SEPARATE PERMIT.
  
 4)PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLY PRIOR TO INSTALLATION.
  
 5)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR DOUBLE
 FRONT ENRTY DOORS WITH TRANSOM, FRENCH
 DOOR AT MASTER B.R. AND FLUSH METAL
 SWINGING DOOR AT GARAGE.
  
 6)PRODUCT APPROVAL SUBMITTAL FORM FOR
 NORANDEX WINDOWS,MULLIONS,AND SLIDING
 GLASS DOORS MUST HAVE WET SIGNATURE,DATE
 AND IMPRESSION SEAL OF ENGINEER CERTIFY-
 ING THE PRODUCTS TO BE ACCEPTABLE.