Plan Review Notes
Plan Review Notes For Permit 00100027
Permit Number 00100027
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)PROVIDE DETAILS ON DRINKING FOUNTAIN.
 FOUNTAIN SHALL BE ON AN ACCESSIBLE
 ROUTE AND PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.FACBC SEC.4.1.2(2),4.3.2(2)
 4.1.3(10)(A),4.3.1.
  
 2)WATER SUPPLY CONTROL FOR DRINKING
 FOUNTAIN AND HOSE BIBB SHALL COMPLY W/
 SPC SEC.610.4.1.
  
 3)SUBMIT SANITARY ISOMETRIC SHOWING
 PIPE SIZE,CONNECTION POINT TO SANITARY
 COLLECTION
  
 4)PVC CANNOT BE USED FOR WATER DIST.
 PER SPC SEC.611.3.
  
 5)SHOW LOCATION OF SANITARY FACILITIES
 FOR THE PARK.SPC SEC.407.1.1.407.1.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.