Plan Review Notes For Permit 00091387 |
Permit Number |
00091387 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) WHERE IS THE FIRE DEPARTMENT | | CONNECTION LOCATED. | | 2) ENTIRE BUILDING IS TO BE COMPLETELY | | FIRE SPRINKLER PROTECTED. THIS INCLUDES | | ALL ELECTRICAL AND MECHANICAL ROOMS. ALL | | VERTICAL SHAFTS ARE ALSO TO BE | | PROTECTED. | | 3) THE FRONT PORCH SHOWN ON THE FIRST | | FLOOR PLAN IF COMBUSTIBLE AND EXCEEDS | | FOUR FEET WIDE IS TO BE FIRE SPRINKLER | | PROTECTED. | | 4) SPARE HEAD BOX AND WRENCH IS TO BE | | PROVIDED. | | 5) SPRINKLER HEADS LOCATED ON BOTH SIDES | | OF THE WINDOWS ARE TO BE LOCATED NO | | FARTHER THAN 1 FOOT OF THE GLASS TO | | PREVENT CRACKING. | | 6) PROVIDE CUT SHEETS ON FIRE SPRINKLER | | HEADS PLANNED FOR USE. |
|