Plan Review Notes
Plan Review Notes For Permit 00091387
Permit Number 00091387
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) WHERE IS THE FIRE DEPARTMENT
 CONNECTION LOCATED.
 2) ENTIRE BUILDING IS TO BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES
 ALL ELECTRICAL AND MECHANICAL ROOMS. ALL
 VERTICAL SHAFTS ARE ALSO TO BE
 PROTECTED.
 3) THE FRONT PORCH SHOWN ON THE FIRST
 FLOOR PLAN IF COMBUSTIBLE AND EXCEEDS
 FOUR FEET WIDE IS TO BE FIRE SPRINKLER
 PROTECTED.
 4) SPARE HEAD BOX AND WRENCH IS TO BE
 PROVIDED.
 5) SPRINKLER HEADS LOCATED ON BOTH SIDES
 OF THE WINDOWS ARE TO BE LOCATED NO
 FARTHER THAN 1 FOOT OF THE GLASS TO
 PREVENT CRACKING.
 6) PROVIDE CUT SHEETS ON FIRE SPRINKLER
 HEADS PLANNED FOR USE.