Plan Review Notes For Permit 00091378 |
Permit Number |
00091378 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD BASED ON HABITABLE | | FLOOR SPACE PER SPC TABLE 407.SEE SEC. | | 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS. | | | | 2)WIDTH OF HANDICAP STALLS SHALL COMPLY | | W/FACBC SEC.4.17.3.(MIN.83"IS REQD.IF | | LAV.IS ADJACENT TO W.C.) | | | | 3)SHT.P0.1-WATER HEATER SHALL BE READILY | | ACCESSIBLE PER SPC SEC.501.7.SUPPLY | | SHIP'S LADDER FOR ACCESSIBILITY,REPAIR | | AND MAINTENANCE. | | | | 4)THE DESIGN OF THE EXISTING SANITARY | | SYSTEM DOESN'T COMPLY W/SPC SEC.914.1. | | REVISE DESIGN TO COMPLY W/CODE. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|