Plan Review Notes For Permit 00091378 |
Permit Number |
00091378 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1.SHEET A1.0 CODE LISTING DATA CALLS FOR | | 2-HOUR TENANT SEPERATION SHEET A3.0 | | SHOWS 1-HOUR WALL.TABLE 701 1997 SBC | | REQUIRES 2-HOUR TENANT SEPERATION | | BETWEEN STORAGE, LOW HAZARD S 2 AND | | BUSINESS OCCUPANCY. | | 2.SHEET A4.0 & A7.0 DOORS 143A 133 A | | SHALL COMPLY WIT SECTION 705 AND | | TABLE 705.1.2 | | 3.SUBMIT PRODUCT APPROVALS FOR IMPACT | | RESISTIANCE WINDOWS AND DOORS/METRO DADE | | COUNTY OR SBCCI | | 4.TYPE 4 CONSTRUCTION REQUIRES ALL | | CONCEALED CONBUSTIABLE LUMBER SHALL | | COMPLY WITH SECTION 707 1997 SBC | | 5.SUBMIT PLANS SHOWING ACCESS COMPLYING | | WITH THE FLORIDA ACCESSIBILITY CODE FOR | | BUILDING CONSTRUCTION 1997 EDITION |
|