2001-01-08 00:00:001.SHEET A1.0 CODE LISTING DATA CALLS FOR
 2-HOUR TENANT SEPERATION SHEET A3.0
 SHOWS 1-HOUR WALL.TABLE 701 1997 SBC
 REQUIRES 2-HOUR TENANT SEPERATION
 BETWEEN STORAGE, LOW HAZARD S 2 AND
 BUSINESS OCCUPANCY.
 2.SHEET A4.0 & A7.0 DOORS 143A 133 A
 SHALL COMPLY WIT SECTION 705 AND
 TABLE 705.1.2
 3.SUBMIT PRODUCT APPROVALS FOR IMPACT
 RESISTIANCE WINDOWS AND DOORS/METRO DADE
 COUNTY OR SBCCI
 4.TYPE 4 CONSTRUCTION REQUIRES ALL
 CONCEALED CONBUSTIABLE LUMBER SHALL
 COMPLY WITH SECTION 707 1997 SBC
 5.SUBMIT PLANS SHOWING ACCESS COMPLYING
 WITH THE FLORIDA ACCESSIBILITY CODE FOR
 BUILDING CONSTRUCTION 1997 EDITION