Plan Review Notes For Permit 00091238 |
Permit Number |
00091238 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)FOR THE FOURTH TIME-THE GRAB BAR | | BEHIND THE WATER CLOSETS IN TOILET ROOMS | | SHALL BE A MIN. OF 36"WIDE PER FACBC | | SEC.4.16.4 AND FIG.29.I SUGGEST YOU READ | | THIS SECTION. | | | | 2)FOR THE FOURTH TIME-SHOW THE REQD. | | CLEAR WHEELCHAIR TURNING SPACE IN THE | | TOILET ROOMS.THE WATER CLOSETS CANNOT | | INFRINGE IN THIS CLEAR SPACE PER FACBC | | SEC.4.2.3. | | | | 3)THE PLUMBING DRAWINGS STILL SHOW THE | | DOORS OF THE TOILET ROOMS SWINGING INTO | | THE CLEAR FLOOR SPACE REQD.FOR THE | | ACCESSIBLE FIXTURES. | | FOR THE FOURTH TIME-DOORS CANNOT SWING | | INTO THE CLEAR FLOOR SPACE REQD.FOR ANY | | FIXTURE.FACBC SEC.4.22.2. | | | | CALL IF YOU HAVE QUESTIONS. | | 561-659-8096,EXT.8377. | | | | TIMOTHY LARGE | | PLUMBINGPLANS EXAMINER |
|