2001-01-08 00:00:001)SHTS.A-1.1,1.2-DOORS CANNOT SWING INTO
 THE CLEAR FLOOR SPACE REQD.FOR THE
 LAVATORIES.FACBC SEC.4.22.2.
  
 2)SHOW THE REQD.WHEELCHAIR TURNING SPACE
 IN EACH TOILET ROOM.COMPLY W/FACBC SEC.
 4.2.3.
  
 3)EACH COMMON AND PUBLIC USE TOILET
 ROOM SHALL BE FULLY ACCESSIBLE PER
 FACBC SEC.4.1.3.(11).
  
 4)SHT.A-1.0-NOTE #F-GRAB BAR BEHIND THE
 WATER CLOSET SHALL BE 36"MIN.PER FACBC
 4.16.4.
  
 5)SUBMIT MANUF.SHEETS FOR TUBAL GAS
 MACHINE,SUCTION MACHINE AND STERILIZ-
 ATION MACHINE.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.