Plan Review Notes
Plan Review Notes For Permit 00091238
Permit Number 00091238
Review Stop M
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED. (RETURN AIR PLENUM SPACE ABOVE
 CEILING IS COMMON AREA FOR ALL AREAS
 AND UNITS.
 CONNECT TO BUILDING FIRE ALARM PER NFPA
 92A 4-4.4.2 OR HORN AND STROBE PER
 4-4.4.3