Plan Review Notes For Permit 00091238 |
Permit Number |
00091238 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)SHTS.A-1.1,1.2-CORRECT THE DOOR SWING | | ON THE TOILET ROOMS.DOORS CANNOT SWING | | INTO THE CLEAR FLOOR SPACE REQD. FOR THE | | LAVATORIES.FACBC SEC.4.22.2. | | | | 2)SHOW THE REQD.WHEELCHAIR TURNING SPACE | | IN EACH TOILET ROOM.COMPLY W/FACBC SEC. | | 4.2.3. | | | | 3)MAX.HEIGHT OF STAFF SINK CABINET SHALL | | COMPLY W/FACBC SEC.4.24.2.SHOW ON SHT. | | A-3. | | | | 4)SHT.A-1-GRAB BAR BEHIND WATER CLOSET | | SHALL BE A MIN. OF 36" NOT 24" AS NOTED | | PER FACBC SEC.4.16.4 | | | | 5)SHT.A-1.0-SHOW THE CLEAR INSIDE | | DIMENSIONS (LXW)OF EACH TOILET ROOM. | | COMPLY W/FACBC SEC.4.16.2.AND FIG.28. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|