Plan Review Notes
Plan Review Notes For Permit 00091238
Permit Number 00091238
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)SHTS.A-1.1,1.2-CORRECT THE DOOR SWING
 ON THE TOILET ROOMS.DOORS CANNOT SWING
 INTO THE CLEAR FLOOR SPACE REQD. FOR THE
 LAVATORIES.FACBC SEC.4.22.2.
  
 2)SHOW THE REQD.WHEELCHAIR TURNING SPACE
 IN EACH TOILET ROOM.COMPLY W/FACBC SEC.
 4.2.3.
  
 3)MAX.HEIGHT OF STAFF SINK CABINET SHALL
 COMPLY W/FACBC SEC.4.24.2.SHOW ON SHT.
 A-3.
  
 4)SHT.A-1-GRAB BAR BEHIND WATER CLOSET
 SHALL BE A MIN. OF 36" NOT 24" AS NOTED
 PER FACBC SEC.4.16.4
  
 5)SHT.A-1.0-SHOW THE CLEAR INSIDE
 DIMENSIONS (LXW)OF EACH TOILET ROOM.
 COMPLY W/FACBC SEC.4.16.2.AND FIG.28.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.