2001-01-08 00:00:00***********DENIED***********************
 1. CONFLICT BETWEEN M-1 AND A-1.0 ON
 EQUIPMENT TYPE
 2. MECH DRAWINGS NOT SIGNED AND SEALED.
 3. NO INFORMATION ON DUCT SMOKE DETECTOR
 OR FAN SHUT DOWN
 4. EXHAUST AIR FANS TO RUN WHEN BUILDING
 IS OCCUPIED TO COMPLY WITH 1997 SMC
 501.2 (AIR BALANCE) NOT OPERATED BY WALL
 SWITCH.
 5. ANY PIPING RELATED TO MEDICAL EQUIP-
 MENT SHALL COMPLY WITH NFPA 99C AND
 REQUIRES MECHANICAL PERMIT. PROVIDE
 DETAILED PLANS FOR WORK SHOWING CODE
 COMPLIANCE PRIOR TO COMENCEMENT OF WORK.