Notes |
Date |
Text |
2001-01-08 00:00:00 | ***********DENIED*********************** | | 1. CONFLICT BETWEEN M-1 AND A-1.0 ON | | EQUIPMENT TYPE | | 2. MECH DRAWINGS NOT SIGNED AND SEALED. | | 3. NO INFORMATION ON DUCT SMOKE DETECTOR | | OR FAN SHUT DOWN | | 4. EXHAUST AIR FANS TO RUN WHEN BUILDING | | IS OCCUPIED TO COMPLY WITH 1997 SMC | | 501.2 (AIR BALANCE) NOT OPERATED BY WALL | | SWITCH. | | 5. ANY PIPING RELATED TO MEDICAL EQUIP- | | MENT SHALL COMPLY WITH NFPA 99C AND | | REQUIRES MECHANICAL PERMIT. PROVIDE | | DETAILED PLANS FOR WORK SHOWING CODE | | COMPLIANCE PRIOR TO COMENCEMENT OF WORK. |
|