Plan Review Notes
Plan Review Notes For Permit 00091222
Permit Number 00091222
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH FIRE SPRINKLER PLANS.
 2) A FOLDED SET OF E2.1 PLANS HAS BEEN
 AMENDED BUT ARE NOT SIGNED AND SEALED
 LIKE THE PLANS. THE E2.1 PLANS DO NOT
 CORRELATE. ORIGINAL E2.1 MUST BE
 REVISED. PLEASE REFER TO FS 61G15-23.002
 471.025
 3) NO INTERIOR FINISH INFORMATION
 PROVIDED.