Plan Review Notes
Plan Review Notes For Permit 00091222
Permit Number 00091222
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) FIRE SPRINKLER DRAWINGS AND HYDRAULIC
 CALCULATIONS ARE TO BE PROVIDED WITH
 PLANS. ACCORDING TO THE PLANS THE FIRE
 SPRINKLERS WILL BE PERMITTED SEPARATELY
 NO BUILDING PERMIT WILL BE ISSUED
 WITHOUT SPRINKLER DRAWINGS.
 2) DOORS 01 AND 12 ARE TO BE EQUIPPED
 WITH SELF-CLOSING DEVICES. WHEN CLOSED
 THESE DOORS ARE REQUIRED TO POSITIVELY
 LATCH
 3) PLEASE INDICATE INTERIOR FINISHES
 FOR EXITS AND OFFICES. THE CURRENT FIRE
 CODE REQUIRES THAT INTERIOR FINISHES
 IN EXITS BE CLASS A OR B. INTERIOR
 FINISHES IN OFFICES CAN BE CLASS A,B,
 OR C.
 4) THE FIRE ALARM NOTES SECTION OF THE
 PLAN INDICATES CLASS B, STYLE C
 CIRCUITS. ONLY CLASS A, STYLE D FIRE
 ALARM CIRCUITS ARE PERMITTED.
 5) PLEASE SUBMIT FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR NEW FIRE ALARM
 EQUIPMENT SHOWN ON PLANS. CUT SHEETS
 ARE TO BE PROVIDED WITH FIRE ALARM
 PLANS.