Plan Review Notes For Permit 00091222 |
Permit Number |
00091222 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) FIRE SPRINKLER DRAWINGS AND HYDRAULIC | | CALCULATIONS ARE TO BE PROVIDED WITH | | PLANS. ACCORDING TO THE PLANS THE FIRE | | SPRINKLERS WILL BE PERMITTED SEPARATELY | | NO BUILDING PERMIT WILL BE ISSUED | | WITHOUT SPRINKLER DRAWINGS. | | 2) DOORS 01 AND 12 ARE TO BE EQUIPPED | | WITH SELF-CLOSING DEVICES. WHEN CLOSED | | THESE DOORS ARE REQUIRED TO POSITIVELY | | LATCH | | 3) PLEASE INDICATE INTERIOR FINISHES | | FOR EXITS AND OFFICES. THE CURRENT FIRE | | CODE REQUIRES THAT INTERIOR FINISHES | | IN EXITS BE CLASS A OR B. INTERIOR | | FINISHES IN OFFICES CAN BE CLASS A,B, | | OR C. | | 4) THE FIRE ALARM NOTES SECTION OF THE | | PLAN INDICATES CLASS B, STYLE C | | CIRCUITS. ONLY CLASS A, STYLE D FIRE | | ALARM CIRCUITS ARE PERMITTED. | | 5) PLEASE SUBMIT FIRE ALARM SYSTEM | | SHOP DRAWINGS FOR NEW FIRE ALARM | | EQUIPMENT SHOWN ON PLANS. CUT SHEETS | | ARE TO BE PROVIDED WITH FIRE ALARM | | PLANS. |
|