Plan Review Notes
Plan Review Notes For Permit 00091180
Permit Number 00091180
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SEE RISER, FEEDERS ARE
 SHOWN AT 400 MCM 320A . NOT RATED FOR
 400A SERVICE.
  
 2)NOTE: RISER AND PANEL SCHEDULE DO NOT
 CORRELATE. ONE SHOWS MCB AND THE OTHER
 MLO. PLEASE CLARIFY.
  
 3)NOTE:PLEASE CLARIFY THE 220V OUTLET
 IN GARAGE. PLEASE SHOW ON PANEL SCHEDULE
  
 4)NOTE: PLEASE SHOWON PANEL THE REQ`D
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372